Hwd

ImageComponentDescriptionSchematics/Mechanics
PLC

SIMATIC S7-300 CPU 319-3 PN/DP: in charge of running the core program of the PIC.

DIGITAL INPUT SM 321: reads the status of the power supplies.

SITOP REDUNDANT POWER SUPPLIES: ensure redundant voltage supply of the PLC.

CIPSPOWER SUPPLY UNIT: containing redundant modules to provide the required +5V and +24V to the electronics.
CIPAANYBUS UNIT: contains HMS Profibus slave modules to share interlock signals between the patch panels and the PLC. It also hosts a CPLD matrix to provide redundacy and fast response for beam dump request propagation to the Beam Interlock System (BIS)EDMS
CIPPATYPE A – PATCH PANEL: provides interface with power converters and quench protection systems. 3A-1B1-1B2-2CEDMS
CIPPBTYPE B – PATCH PANEL: provides interface with power converters and quench protection systems. 8B1EDMS
CIPPCTYPE C – PATCH PANEL: provides interface with power converters and quench protection systems. 1B1-2B2-8CEDMS
CIPPSTYPE S – PATCH PANEL: provides interface with power converters, quench protection systems, uninterruptable power supplies, arret d’urgence and beam interlock system. 1A-2B2-5C-specialEDMS
CIPIDAUGHTER BOARD: Generic board for patch panel which provides current sources to the loops and optocouplers for reading purposes.EDMS